Negative Sequence Current Using Positive Sequence Current And Sequence Impedances(LLGF) Calculator

Formula Used:

\[ I_2 = -I_1 \times \frac{Z_0 + 3 \times Z_f}{Z_0 + Z_2 + 3 \times Z_f} \]

A
Ω
Ω
Ω

Unit Converter ▲

Unit Converter ▼

From: To:

1. What Is Negative Sequence Current?

Negative Sequence Current consists of balanced three-phase current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation. It's an important parameter in power system analysis, particularly for fault analysis and protection system design.

2. How Does The Calculator Work?

The calculator uses the formula:

\[ I_2 = -I_1 \times \frac{Z_0 + 3 \times Z_f}{Z_0 + Z_2 + 3 \times Z_f} \]

Where:

Explanation: This formula calculates the negative sequence current during a Line-to-Line-to-Ground (LLGF) fault using positive sequence current and sequence impedances.

3. Importance Of Negative Sequence Current Calculation

Details: Accurate calculation of negative sequence current is crucial for power system protection design, fault analysis, and ensuring the stability and reliability of electrical power systems. It helps in setting protective relays and designing appropriate protection schemes.

4. Using The Calculator

Tips: Enter all impedance values in ohms (Ω) and current values in amperes (A). Ensure that the denominator (Z₀ + Z₂ + 3×Zf) is not zero to avoid division by zero errors.

5. Frequently Asked Questions (FAQ)

Q1: What is the significance of negative sequence current in power systems?
A: Negative sequence current indicates unbalance in the system and can cause heating in generators and motors. It's used for protection against unsymmetrical faults.

Q2: When is this formula specifically applicable?
A: This formula is specifically used for Line-to-Line-to-Ground (LLGF) fault analysis in three-phase power systems.

Q3: What do the sequence impedances represent?
A: Sequence impedances represent the impedance offered to positive, negative, and zero sequence currents in a power system network.

Q4: Why is there a negative sign in the formula?
A: The negative sign indicates that the negative sequence current is 180 degrees out of phase with the positive sequence current component.

Q5: What are typical values for sequence impedances?
A: Sequence impedance values vary depending on the system components. Positive and negative sequence impedances are usually similar, while zero sequence impedance can be significantly different.

Negative Sequence Current Using Positive Sequence Current And Sequence Impedances(LLGF) Calculator© - All Rights Reserved 2025